PET-7060
6-channel Power Relay Output (Digital Output) and 6-channel Isolation Digital Input (32-bit Counters) Data Acquisition, communicable and Powered over Ethernet and Modbus TCP Protocol. Replacement for PETL-7060.
Features
PET-7060 is a web-based PoE Ethernet I/O module that features a built-in web server, which allows configuration, I/O monitoring and I/O control through a regular web browser. It provides power relay output and digital input over Modbus TCP. It is powered over Ethernet so data and power can come from the Ethernet cable. With the web HMI function, no programming or HTML skills are needed. Creating dynamic and attractive web pages for I/O monitoring and I/O control can be fun for engineers after all. PET-7060 offers easy and safe access for users anytime and anywhere! PET-7060 also supports Modbus/TCP protocol that makes perfect integration for PET-7060 to SCADA software.
Power-over-Ethernet (PoE) allows power and data to be carried over a single Ethernet cable so a device can operate solely from the power it receives through the Ethernet data cable. This innovation allows greater flexibility in office design, higher efficiency in systems design, and faster turnaround time in set-up and implementation.
PET-7060 features true IEEE 802.3af-compliant (classification, Class 1) Power over Ethernet (PoE) using both Ethernet pairs (Category 5 Ethernet cable). PET-7060 can receive power from auxiliary power sources like AC adapters and batteries in addition to the PoE enabled network. This is a desirable feature when the total system power requirements exceed the PSE's load capacity. With the auxiliary power option, the PET-7060 can be used in standard Ethernet (non-PoE) systems.
The PET-7060 provides 6 power relay (form A) output and 6 isolated wet contact (sink, source type) digital input channels. Each power relay supports contact rating as 5A@250VAC or 5A@30VDC and each digital input channel supports counter input (32 bits and 500Hz max.)
- IEEE 802.3af-compliant Power over Ethernet (PoE)
- Built-in Web Server
- Modbus/TCP Protocol
- Communication Security
- 2-way Isolation/ESD Protection
- Built-in Dual Watchdog
- 10/100 Base-TX Ethernet
- I/O Pair Connection
- DO Type: 6 Power Relay (Form A)
- DI Type: 6 Wet Contact (Sink/Source)
- PoE Digital Input
- PoE Digital Output
- Powered over Ethernet
Specifications
Software | |||
Built-In Web Server | Yes | ||
Web HMI | Yes | ||
I/O Pair Connection | Yes | ||
Communication | |||
Ethernet Port | 1 x RJ-45, 10/100 Base-TX | ||
PoE | Yes | ||
Protocol | Modbus/TCP, Modbus/UDP | ||
Security | ID, Password and IP Filter | ||
Dual Watchdog | Yes, Module (0.8 second), Communication (Programmable) | ||
LED Indicators | |||
for System Running | Yes | ||
for Ethernet Link/Act | Yes | ||
for DI/DO status | - | ||
for PoE Power | Yes | ||
2 Way Isolation | |||
Ethernet | - | ||
I/O | 3000 VDC | ||
EMS Protection | |||
ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal and ±8 kV Air for Random Point | ||
EFT (IEC 61000-4-4) | ±2 kV for Power Line | ||
Surge (IEC 61000-4-5) | ±0.5 kV for Power Line | ||
Power Requirements | |||
Reverse Polarity Protection | Yes | ||
Powered from Terminal Block | 12 ~ 48 VDC | ||
Powered PoE | Yes, IEEE 802.3af, Class1 | ||
Consumption | 2.8 W (Max.) | ||
Mechanical | |||
Dimensions (W x L x H) | 72 mm x 123 mm x 35 mm | ||
Required Supply Voltage | DIN-Rail or Wall mounting | ||
Environment | |||
Operating Temperature | -25°C ~ +75°C (-13°F ~ +167°F) | ||
Storage Temperature | -30°C ~ +80°C (-22°F ~ +176°F) | ||
Relative Humidity | 10 ~ 90% RH, Non-condensing |
I/O Specification
Digital Input/Counter | |||
Channels | 6 | ||
Contact | Wet Contact | ||
Sink/Source (NPN/PNP) | Sink/Source | ||
On Voltage Level | +10 VDC ~ +50 VDC | ||
Off Voltage Level | +4 VDC Max. | ||
Input Impedance | 10kΩ | ||
Counters | Max. Count | 4,294,967,285 (32 bits) | |
Max. Input Frequency | 500 Hz | ||
Min. Pulse Width | 1 ms | ||
Overvoltage Protection | +70 VDC | ||
Power Relay | |||
Channels | 6 | ||
Type | Power Relay, Form A (SPST N.O.) | ||
Contact Rating | 5 A @ 250 VAC/24 VDC (Resistive Load) | ||
Min. Contact Load | 10 mA @ 5 V | ||
Operating Time | 10 ms (max.) | ||
Release Time | 5 ms (max.) | ||
Mechanical Endurance | 2 × 10^7 ops | ||
Electrical Endurance | 10^5 ops. | ||
Power-on Value | Yes, Programmable | ||
Safe Value | Yes, Programmable |