Features
- 9 Signal Relay Output channels
- 4 kV ESD Protection
- 3750 VDC Intra-module Isolation
- Configurable Power-on Value Settings
- Configurable Safe Value Settings
Introduction
The XV119 provides 9 Form A Signal relay output channels. The XV119 also provides options for configuring power-on and safe digital output values. 4 kV ESD protection and 3750 VDC intramodule isolation are also provided to enhance noise immunity capabilities in industrial environments.
Specifications
Isolation | |
Intra-module Isolation | 3750 VDC |
EMS Protection | |
ESD (IEC 61000-4-2) | ±4 kV Contact For Each Terminal ±8 kV Air For Random Terminal |
Relay Output | |
Channels | 9 |
Type | Signal Relay (Form A) |
Contact Material | Silver Nickel, Gold-covered |
Contact Rating | 2 A @ 30 VDC 0.24 A @ 220 VDC 0.25 A @ 250 VAC |
Operate Time | 3 ms (typical) |
Release Time | 4 ms (typical) |
Electrical Endurance | 2 x 10^5 ops. |
Mechanical Endurance | 10^8 ops. |
Power on Value | Yes |
Safe Value | Yes |
COM Ports | |
Baud Rate | 115200 bps |
Data Format | N, 8, 1 |
Protocol | Modbus/RTU |
Power | |
Consumption | 1.2 W Max |
Powered from Terminal Block | 5 VDC |
Mechanical | |
Dimensions (mm) | 59 mm x 82 mm x 13 mm (W x L x H) |
Environmental | |
Operating Temperature | -25 ~ +75°C |
Storage Temperature | -30 ~ +80°C |
Humidity | 10 ~ 90% RH, Non-condensing |