Download Now

Enter your information or login to view the document.


×
16 Channel Differential Analog Input Module with Thermocouple, Voltage and Current Input types. Communicable over DCON and Modbus Protocols.

M-6018-16

16 Channel Differential Analog Input Module with Thermocouple, Voltage and Current Input types. Communicable over DCON and Modbus Protocols.

  Price:  $529.00  

Fastest Delivery: (Details) X Delivery Details
We ship via UPS and fastest delivery is with Next Day Air. UPS Next Day Air Early typically gets their product to them as early as 8am, Next Day Air gets their product typically there by 10:30am and Next Day Air Saver typically by 3pm. We ship same day for in stock items and the lead time is up to one week for out of stock items. Delivery is dependent on UPS and your shipping method.
ADD TO CART
ADD TO CART
BUY BY 1-CLICK

References & Support


Features

ICP DAS USA’s M-6018-16 is an analog input module is equipped with 16 differential analog input channels. The M-6018-16’s voltage input range can be from ±15 mV to ±2.5 V, the current input range can be either +4 to +20 mA, 0 to +20 mA, or ±20 mA, and types J, K, T, E, R, S, B, N, C, L, M, LDIN43710 thermocouple can be used for the thermocouple input. Overvoltage protection of up to 120 VDC is provided. The module also features per-channel open wire detection for the thermocouple input types, and provides 4 kV ESD protection as well as 3000 VDC intra-module isolation.

  • 16-channel Diff erential Analog Input
  • ±120 VDC Overvoltage Protection
  • Current, Voltage or Thermocouple Input
  • 3000 VDC Intra-module Isolation
  • Adjustable CJC off set
  • Open Thermocouple Detection
  • Dual Watchdog
  • Wide Operating Temperature Range: -25°C to +75°C

Applications

  • Building Automation
  • Factory Automation
  • Machine Automation
  • Remote Maintenance
  • Remote Diagnosis
  • Testing Equipment

Specifications

I/O Specifications

Analog Input

Channels

16

Wiring

Differential

Sensor Types

Thermocouple

Voltage

Current

J, K, T, E, R, S, B, N, C

±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V

±20 mA, 0 ~ +20 mA, +4 ~ +20 mA (requires an optional external 125 ? resistor)

Voltage

±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V

Current

±20 mA, 0 ~ +20 mA, +4 ~ +20 mA (requires an optional external 125 Ω resistor)

Resolution

16-bit

Accuracy

0.1% of FSR

Sampling Rate

10 Hz (Total)

Input Impedance

> 400 kΩ

Common Voltage Protection

25 VDC

Individual Channel Configuration

-

Overvoltage Protection

120 VDC

Open Wire Detection (for thermocouple only)

Yes

Temperature Outputs Consistency

-

Stable Temperature Output in the Field

-

System Specifications

Communication

Interface

RS-485

Bias Resistor

Switch Selectable (1 kΩ resistor)

Format

(N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1)

Baud Rate

1200 to 115200 bps

Protocol

Modbus RTU, DCON

Dual Watchdog

Yes, Module (1.6 Seconds), Communication (Programmable)

LED Indicators/Display

System LED Indicator

Yes, 1 as Power/Communication Indicator

I/O LED Indicators

-

7-segment LED Display

-

Isolation

Intra-module Isolation, Field-to-Logic

3000 VDC

EMS Protection

ESD (IEC 61000-4-2)

±4 kV Contact for each Terminal

±8 kV Air for Random Point

EFT (IEC 61000-4-4)

±4 kV for Power Line

Surge (IEC 61000-4-5)

±1 kV for Power Line

Power

Reverse Polarity Protection

Yes

Input Range

+10 ~ +48 VDC

Consumption

0.5 W

Mechanical

Dimensions (L x W x H)

120 mm x 116 mm x 64 mm

Installation

DIN-Rail or Wall Mounting

Environment

Operating Temperature

-25 to +75°C

Storage Temperature

-40 to +85°C

Relative Humidity

10 to 95% RH, Non-condensing

References and Support