ET-7017
8-channel Voltage Input, Current Input, Analog Input with High Voltage Protection and 4-channel Isolated Digital Output Data Acquisition Module, communicable over Ethernet and Modbus TCP Protocol. Supports operating temperatures between -25°C to 75°C (-13°F ~ +167°F.
Features
The ET-7017, a web-based Ethernet I/O module, features a built-in web server, which allows configuration, I/O monitoring and I/O control by simply using a regular web browser. With the web HMI function, no more programming or HTML skills are needed. You can create dynamic and attractive web pages for I/O monitoring and I/O control. The ET-7017 offers easy and safe access for users from anytime and anywhere! The ET-7017 also supports Modbus/TCP protocol that makes seamless integration to SCADA software.
The ET-7017 is a 16-bit, 8-channel differential analog inputs and 4-channel digital ouputs module that provides programmable input range on all analog channels(+/-150mV, +/-500mV, +/-1V, +/-5V, +/-10V, +/-20mA, 0~20mA and 4~20mA) and digital output can be set alarm output. Each analog channel is allowed to configure an individual range and has 240Vrms high over voltage protection. Jumper selectable for voltage or current input.The ET-7017 is designed for applications to industrial monitoring and measurement; therefore, we have made it tough enough to survive harsh environments. The module contains 2-way isolation from noise and surges, one for digital inputs and the other for Ethernet. The ET-7000 has got a wide range of power input (10~30VDC) and operating temperature of -25°C ~ +75°C (-13°F ~ +167°F).
Specifications
CPU | |
CPU | 80186 CPU (80MHz) |
SRAM | 512K Bytes |
Flash Memory | 512K Bytes |
EEPROM | 16K Bytes |
Dual Watchdog | Yes |
Communication | |
Ethernet Port | 10 / 100 Base-TX (With Link, Activity LED Indicator) Automatic MDI/MDI-X Crossover |
Analog Input | |
Input Channels | 8 Differential |
Input Type | ±150mV, ±500mV, ±1V, ±5V, ±10V ±20mA, 0~20mA, 4~20mA (jumper selectable) |
Resolution | 16-bit (Normal Mode) / 12-bit (Fast Mode) |
Sampling Rate | 10 samples/ second (Normal Mode) / 50 samples/ second (Fast Mode) total |
Accuracy | ±0.1% (Normal Mode) / ±0.5% (Fast Mode) or better |
BandWidth | 15.7Hz (Normal Mode) / 78.7Hz (Fast Mode) |
Zero drift | ±20uV/°C |
Span drift | ±25ppm/°C |
Input Impedance | Voltage: 2M Ω, Current: 125 Ω |
Common Mode Rejection | 86dB min. |
Normal Mode Rejection | 100dB |
Over Voltage Protection | 240 Vrms |
ESD Protection | 4KV Contact for each terminal, and 8KV Air for random point |
EFT Protection | 4KV for Power |
Digital Output | |
Output Channels | 4 (Sink) |
Output Type | Isolated Open-Collector |
Max Load Current | 700mA/ Channel |
Load Voltage | 5Vdc to 50Vdc |
2 Way Isolation | |
Ethernet | 1500V DC |
AI and DO | 2500V DC |
Mounting | |
Din Rail Mount | Yes |
Wall Mount | Yes |
LED Display | |
L1 LED | as Run indicator |
L2 LED | as Link/Act indicator |
L3 LED | as 10/100M indicator |
Power Requirements | |
Protection | Power reverse polarity protection |
Required Supply Voltage | +10Vdc to 30Vdc (non-regulated) |
Power consumption | 0.10A/24V DC |
Environment | |
Operating Temperature | -25°C to +75°C |
Storage Temperature | -30°C to +80°C |
Relative Humidity | 5% to 90% Non-condensing |
Dimensions | |