The DNM-844 is 4-channel current transformer. The maximum current input range is from ±2000 A can be attenuated to ±10 V. It provides3000 VDC intra-modules isolation. It can be used with the analog input modules such as I-7017, I-87017, M-7017RMS and I-87017W-RMSetc. to measure the high current.
Specifications
EMS Protection | |
---|---|
ESD (IEC 61000-4-2) | ±4 kV contact for power line, input and output channels, ±8 kV air for random point |
Surge (IEC 61000-4-5) | ±3 kV for power liner |
CT | |
---|---|
Type | Clip |
Inside Diameter | Φ21 mm |
Leading Cable | 1.5 m |
Analog Input | |
---|---|
Channels | 4 |
Type | AC/DC Current |
Range | High Current: ±200 A |
Accuracy | 1% of FSR |
Bandwidth | 0 - 50 KHz |
Intra-module Isolation | 3000 VDC |
Isolation | 2.5 KV @ 50 (60) HZ/1 min |
Analog Output | |
---|---|
Channels | 4 |
Type | AC/DC Voltage |
Range | High Voltage: ±10 VDC or 10 VAC |
Accuracy | 1% of FSR |
Isolation | 2.5 KV @ 50 (60) HZ/1 min |
Power | |
---|---|
Input Range | +10 VDC - +30 VDC |
Consumption | 2.3 W |
Mechanical | |
---|---|
Casing | Metal |
Dimensions (mm) | 103 x 104 x 28 (W x L x D) |
Installation | DIN-Rail Mounting |
Environment | |
---|---|
Operating Temperature | -25 - +75 Degrees Celsius |
Storage Temperature | -30 - +75 Degrees Celsius |
Humidity | 10 - 90% RH, Non-condensing |