IP-8847
ISaGRAF IEC-61131-3 PAC with 8 I/O Slots. Has Ethernet, RS-232, and RS-485 ports. Supports programming in Ladder Logic, Structured Text, Function Block Diagram, Instruction List and Flow Chart. Replacement Item for I-8837-80
Features
The ISaGRAF iPAC-8000 Series (iP-8417/8817/8447/8847) is the ISaGRAF SoftLogic PAC from ICP DAS. Each WP-8xx7 is equipped with an 80186, 80 MHz CPU running a MiniOS7 operating system, a variety of input/output ports (Dual 10/100 Base-TX Ethernet Ports for iP-8x47, one RS-232/485 port, one RS-485 port and two RS-232 ports) and a range of I/O slots (4/8) that can be used to integrate high performance parallel I/O modules (high profile I-8K Series) or serial I/O modules (high profile I-87K series). Users can also choose RS-485 Remote I/O modules (I-7000 series) or expansion units (RU-87Pn or I-87Kn) plugged with high profile I-87K serial I/O modules. Compared to I-8xx7, iPAC-8xx7 series is 2 ~ 4 times faster!
Highlight Information
- 80186, 80 MHz CPU
- MiniOS7 Inside
- Development Software: ISaGRAF Ver.3
- 512 KB Battery Backup SRAM to Retain Data
- 64-bit Hardware Serial Number
- 4/8 Hot-Swap Slots for I-87K High Profile I/O Modules
- 4 Serial Ports (RS-232/485)
- 64-bit Hardware Serial Number
- Redundant Power Inputs
- Operating Temperature: -25 ~ +75 °C
Software Feartures
- MiniOS7 Embedded Operating System (DOS-like)
- Embedded ISaGRAF Ver.3 SoftLogic
- Support IEC 61131-3 Standard
- Accepts max. 64 KB ISaGRAF code size
Hardware Feartures
- 80186 CPU (16-bit & 80 MHz)
- Dual Battery Backup SRAM (512 KB)
- 64-bit Hardware Serial Number for Protection
- 4/8 I/O Expansion Slots (support High Profile I/O Modules)
- Support I/O Module Hot Swap
- Dual 10/100M Ethernet Ports (for iP-8x47)
- 4 Serial Ports (RS-232/485)
- Redundant Power Inputs
Applications
Measure Humidity and Temperature Values via DL-100TM485 ISaGRAF PAC connects the Smart Meter ZigBee Wireless Solution- Stress Monitoring Application of Constructions
- GPS Applications: ISaGRAF PAC plus I-87211W or GPS-721
- Integrate with CAN/CANopen Devices and Sensors
- Send Email with One Attached File
- An Easy Way to Program the Fast FRnet Remote I/O Modules
- Modbus RTU/TCP Slave Ports
- Modbus RTU/ASCII Master Ports
- Remote I/O Modules and Expansion module/board
- SMS: Short Message Service
- Motion Control
- Data Recorder and Data Logger
- Data Exchange: Fbus or Ebus
- Detect I-8K/I-87K I/O status
- VIP Communication Security
- As a Modbus Gateway for the Remote I/O Modules
Note: Some of the applications don't support iP-8x17, please click the item for more details.
Click here for "Applications Supporting List" & all applicationsSpecifications
Models | iP-8847 | ||||
System Software | |||||
OS | MiniOS7 (DOS-like embedded operating system) | ||||
Development Software | |||||
ISaGRAF Software | ISaGRAF Ver. 3 | IEC 61131-3 standard | |||
Languages | LD, ST, FBD, SFC, IL & FC | ||||
Max. Code Size | 64 KB | ||||
Scan Time | 2 ~ 25 ms for normal program | ||||
10 ~ 125 ms (or more) for complex or large program | |||||
CPU Module | |||||
CPU | 80186, 80 MHz | ||||
SRAM | 768 KB | ||||
Flash | 512 KB; with Write Protect Switch | ||||
microSD Expansion | Yes (but ISaGRAF doesn't support) | ||||
OS | MiniOS7 (DOS-like embedded operating system) | ||||
Dual Battery Backup SRAM | 512 KB; data valid up to 5 years (for retain variables) | ||||
EEPROM | 16 KB | ||||
NVRAM | 31 bytes (battery backup, data valid up to 5 years) | ||||
RTC (Real Time Clock) | Provide second, minute, hour, date, day of week, month, year | ||||
64-bit Hardware Serial Number | Yes, for Software Copy Protection | ||||
EEPROM | 16 KB | ||||
Watchdog Timers | Yes (0.8 second) | ||||
DIP Switch | Yes (8 bits) | ||||
Communication Ports | |||||
Ethernet | RJ-45 x 2, 10/100 Base-TX (Auto-negotiating, Auto MDI/MDI-X, LED indicators) | ||||
COM 0 | Internal communication with the high profile I-87K series modules in slots | ||||
COM 1 | RS-232 (to update firmware) (RxD, TxD and GND); non-isolated | ||||
COM 2 | RS-485 (Data+, Data-) with internal self-tuner ASIC; 3000 VDC isolated | ||||
COM 3 | RS-232/RS-485 (RxD, TxD, CTS, RTS and GND for RS-232, Data+ and Data- for RS-485); non-isolated | ||||
COM 4 | RS-232 (RxD, TxD, CTS, RTS, DSR, DTR, CD, RI and GND); non-isolated | ||||
SMMI | |||||
LED Display | Yes, 5-Digit | ||||
Programmable LED Indicators | 3 | ||||
Push Buttons | 4 | ||||
Buzzer | yes | ||||
I/O Expansion Slots | |||||
Slot Number | 8 | ||||
Note: For High Profile I-8K and I-87K Modules Only | |||||
Data Bus | 8/16 bits | ||||
Address Bus Range | 2 K for each slot | ||||
Mechanical | |||||
Dimensions (W x L x H) | 231 mm x 132 mm x 111 mm: iP-8417, iP-8447 | ||||
355 mm x 132 mm x 111 mm: iP-8817, iP-8847 | |||||
Installation | DIN-Rail or Wall Mounting | ||||
Environmental | |||||
Operating Temperature | -25 ~ +75°C | ||||
Storage Temperature | -30 ~ +80°C | ||||
Ambient Relative Humidity | 10 ~ 90% RH (non-condensing) | ||||
Power | |||||
Input Range | +10 ~ +30 VDC (non-condensing) | ||||
Isolation | 1 kV | ||||
Redundant Power Inputs | Yes, with one power relay (1 A @ 24 VDC) for alarm | ||||
Capacity | 30 W | ||||
Consumption | 7.2 W | ||||
Protocols (Note that certain protocols require optional devices) | |||||
NET ID | 8 bits DIP switch to assign NET ID as 1 ~ 255 | ||||
Modbus RTU/ASCII Master | A max. of 2 ports: COM1~5. (To connect to other Modbus Slave devices.) A max. of Modbus_xxx Function Block amount for 2 ports: 128. (*) |
||||
Modbus RTU Slave | A max. of 2 ports: COM1 and one of COM2 ~ 3. (For connecting ISaGRAF, PC/HMI/OPC Server and HMI panels.) |
||||
Modbus TCP/IP Slave | (For iP-8x47 only) Two Ethernet ports support Modbus TCP/IP Slave Protocol for connecting ISaGRAF & PC/HMI up to 6 connections. | ||||
User-defined Protocol | Custom protocols can be applied at COM1~20 using Serial communication function blocks. (*) | ||||
Remote I/O | One of COM2 ~ 4 supports I-7000 I/O modules, I-87K base + I-87K Serial I/O boards, or RU-87Pn + I-87K High Profile I/O boards as remote I/O. A max. of 64 I-7000/87K remote I/O modules can connect to one PAC. | ||||
Fbus | Built-in COM3 Port to exchange data between ICP DAS’s ISaGRAF PACs. | ||||
Ebus | (LAN2: upper port of iP-8x47 ONLY) Used to exchange data between ICP DAS ISaGRAF Ethernet PACs via the Ethernet port. |
||||
Send Email | (For iP-8x47 only) Provide functions to send email to a max. of 10 receivers with a single attached file via the Ethernet port through internet. The max. of file size is about 488 KB. |
||||
SMS: Short Message Service | One of COM4 ~ 5 can link to a GSM Modem to support SMS. The user can request data/control the controller via a cellular phone. The controller can also send data and alarms to the user’s cellular phone. (*) Optional GSM Modem: GTM-201-RS232 (850/900/1800/1900 GSM/GPRS External Modem). |
||||
Modem Link | COM4 can connect a general Modem. Supports PC to remotely download & monitor the controller. | ||||
MMICON/LCD | One of COM3 or COM4 supports ICP DAS’s MMICON. The MMICON is featured with a 240 x 64 dot LCD and a 4 x 4 Keyboard. User can use it to display picture, string, integer, float, and input a character, string, integer and float. | ||||
Redundant Bus7000 | Two ISaGRAF PACs can link to remote I-7000 & I-87K High profile I/O modules at the same time. Only one controller is active to control these Remote I/Os. If one is dead, the other one will take over the control of Remote I/Os. | ||||
CAN/CANopen | COM1 or COM3 ~ 12 can connect to one I-7530 (converter: RS-232 to CAN) to support CAN/CANopen devices and sensors. One iP-8xx7 supports a max. of 3 RS-232 ports to connect a max. of 3 I-7530. (*) (FAQ-086) | ||||
FRnet I/O | Enable a max. of 4 pcs. I-8172W boards to be used to connect to FRnet I/O modules, such as FR-2053, FR-2057, FR-32R, FR-32P. (Max. 1024-ch. DI + 1024-ch. DO) (FAQ-082, 154) | ||||
FTP Client | Enable the FTP Client to upload files from the PAC to a remote FTP server on a PC. (FAQ-151) | ||||
Optional I/O Functions (Refer to the ISaGRAF PAC I/O Selection Guide for I/O Module list) | |||||
PWM Output | High Speed PWM Module | I-8088W, 8-ch PWM outputs, software support 1 Hz ~ 100 kHz (non-continuous), duty: 0.1 ~ 99.9 | |||
DO Module as PWM | 8-ch max. for one controller. 500 Hz max. For Off=1 & On=1 ms Output Square Curve: Off: 1 ~ 32767 ms, On: 1 ~ 32767 ms. Optional DO Boards: I-8037W, 8041W, 8041AW, 8042W, 8050W, 8054W, 8055W, 8056W, 8057W, 8060W, 8063W, 8064W, 8068W, 8069W. (Relay Output boards cannot generate fast square wave) |
||||
Counters, Encoder, Frequency | Parallel DI Counter | 8-ch. max. for 1 controller. Counter Val: 32-bit.; 500 Hz max. Min. ON & OFF width must > 1 ms Optional DI boards: I-8040W, 8040PW, 8042W, 8046W, 8050W, 8051W, 8052W, 8053W, 8053PW, 8054W, 8055W, 8058W, 8063W. | |||
Serial DI Counter | Counter input: 100 Hz max. Counter value: 0 ~ 65535 (16-bit) Optional serial I-87K DI boards: I-87040W, 87046W, 87051W, 87052W, 87053W, 87053W-A5, 87054W, 87055W, 87058W, 87059W, 87063W. | ||||
Remote DI Counter | All remote I-7000/I-87K DI modules support counters. 100 Hz max. value: 0 ~ 65535 | ||||
High Speed Counter | I-87082W: 100 kHz max. 32-bit; I-8084W: 250 kHz max. 32-bit |
||||
Encoder | I-8093W: 3-axis Encoder Module, max. 1M Hz for quadrant input mode, max. 4M Hz for pulse/direction and cw/ccw input mode. (FAQ-112) I-8084W: 250 kHz max. , 4-ch encoder, can be Dir/Pulse, or Up/Down or A/B phase (Quad. mode); Not support Encoder Z-index. (FAQ-100). |
||||
Frequency | I-87082W: 2-ch, 1 Hz ~ 100 kHz; I-87088W: 8-ch, 1 Hz ~ 100 kHz; I-8084W: 8-ch, 1 Hz ~ 250 kHz; |
||||
Motion | Motion Control | Can integrate with one I-8091W (2-axis) or two I-8091W (4-axis) to do motion control. Ethernet communication is also available when doing motion control. | |||
* Note: The COM5 ~ COM20 ports are located in the expansion boards if they are installed in slots 0 ~ 7 of iP-8xx7. * ISaGRAF FAQ: www.icpdas.com > Support > FAQ > ISaGRAF Soft-Logic PAC * ICP DAS recommends using NS-205/NS-208 or RS-405/408 (Ring Switch) Industrial Ethernet Switches. |