ET-7245
Dual Ethernet port Modbus TCP DAQ module with 16 source-type digital output channels
Features
- Built-in Web Server
- Web HMI
- Support for both Modbus TCP and Modbus UDP Protocols
- Communication Security
- 2-port Ethernet Switch for Daisy-Chain Topology
- Dual Watchdog
- Wide Operating Temperature Range: -25 ~ +75°C
- I/O Pair Connection
- Built-in I/O
- Source-type DO: 16 Channels
Introduction
The ET-7245 provides 16 source-type digital output channels. It features optical isolation for 3750 VDC of transient overvoltage protection and doesn’t have channel-to-channel isolation. The power-on value and safe value of digital output channelare programmable. In some industrial applications, the user can connect the output channel of ET-7245 to the RM series relay module to switch inductive loads.
Applications
Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote Diagnosis, Testing Equipment.
Specifications
Software | |
Built-in Web Server | Yes |
CPU Module | |
Watchdog Timer | Yes, Module (0.8 second), Communication (Programmable) |
EMS Protection | |
EFT (IEC 61000-4-4) | ±4 kV for Power Line |
ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal ±8 kV Air for Random Point |
Surge (IEC 61000-4-5) | ±2 kV for Power Line |
LED Indicators | |
Status | 1 x Power, 2 x Ethernet, 16 x I/O |
Digital Output | |
Channels | 16 |
Type | Isolated Open Source |
Sink/Source (NPN/PNP) | Source |
Load Voltage | +10 VDC ~ +40 VDC |
Load Current | 600 mA/channel |
Overvoltage Protection | 47 VDC |
Overload Protection | 1.4 A (with short-circuit protection) |
Short-circuit Protection | Yes |
Power on Value | Yes, Programmable |
Safe Value | Yes, Programmable |
Ethernet | |
Ports | 2 x RJ-45, 10/100 Base-TX, Swtich Ports |
Security | ID, Password and IP Filter |
Protocol | Modbus/TCP, Modbus/UDP |
Power | |
Reverse Polarity Protection | Yes |
Consumption | 3.0 W |
Powered from Terminal Block | 12 ~ 48 VDC |
Mechanical | |
Dimensions (mm) | 76 mm x 120 mm x 38 mm (W x L x H) |
Installation | DIN-Rail or Wall mounting |
Environmental | |
Operating Temperature | -25 ~ +75°C |
Storage Temperature | -30 ~ +80°C |