8-channel Thermistor Input (Analog Input) and 4-channel Isolated Digital Output PoE Modbus TCP Protocol Module. Built-in Web Server, with operating temperature range of -25°C ~ +75°C (-13° ~ +167°F)
Features
WISE (Web Inside, Smart Engine) is a product series developed by ICP DAS that functions as control units for use in remote logic control and monitoring in various industrial applications. WISE offers a user-friendly and intuitive web site interface that allows users to implement IF-THEN-ELSE control logic on controllers just a few clicks away; no programming is required. With its powerful and easy-to-use features, it will minimize the learning curve, shorten time to market and dramatically reduce the effort and cost spent on system development.
WISE-7105 follows IEEE 802.3af-compliant (classification, Class 1) Power over Ethernet (PoE) specification. It allows receiving power from PoE enabled network by Ethernet pairs (Category 5 Ethernet cable). This feature provides greater flexibility and higher efficiency therefore simplifying systems design, saving space, reducing cables and eliminating the requirement for dedicated electrical outlets. Meanwhile, in case under a non-PoE environment, WISE-7105 will still be able to receive power from auxiliary power sources like AC adapters or battery, etc.
This multi-function module WISE-7105 supports Modbus/TCP protocol to make seamless integration with SCADA software available. It features 16-bit, 8-channel Thermistor inputs and 4-channel digital outputs. Each analog channel is allowed to configure an individual range.
- Built-in Web Server for IF-THEN-ELSE rule setting
- Built-in IF-THEN-ELSE rule enigne for logic operation
- No more programming. Just click and get done!
- Support IO, Counter, Timer, Email operations
- Modbus/TCP Protocol for SCADA Software Seamless Integration
- IEEE 802.3af-compliant Power over Ethernet (PoE)
- 10/100 Base-TX Ethernet
- Support Thermistor Input
- Individual Channel Configuration
- 4-channel Digital Outputs
- 2-way Isolation/ESD Protection
Specifications
|
Software Specifications
Functions | |
36 IF-THEN-ELSE Logic Rules | 3 IF conditions with AND or OR operators 3 THEN actions 3 ELSE actions |
48 Internal Registers | Hold temporary variables and read/write data via Modbus/TCP address. |
12 Timers | Delay / Timing functions. |
12 Emails | Send Email messages to pre-set Email receivers. |
12 CGI Commands | Send pre-set CGI commands. |
12 Receipts | Set up Then/ELSE action groups. |
Rule Configuration Website | Access Web server on WISE controllers to edit and upload logic rules through web browser. |
Modbus/TCP Protocol | Real time control and monitoring I/O channels and system status of controllers via SCADA software. |
IF Conditions | |
AI Channel | ON、OFF、ON to OFF、OFF to ON、Change |
Internal Register | =、>、<、>=、<=(value) |
Rule Status | Enable、Disable |
P2P | DI、AI、DI counter、DO counter、IR |
DO Counter | =、>、<、>=、<=(value)、Change |
Timer | Timeout、Not Timeout |
THEN / ELSE Actions | |
DO Channel | ON、OFF、Pulse Output |
Internal Register | Change the value |
DO Counter | Reset |
Timer | Start、Stop |
Start、Stop | |
CGI Commands | |
Recipe | Execute |
P2P | DO(On/Off)、AO、IR |
Rule Status | Enable、Disable |