10 Channel Analog Input Data Acquisition Module, supports Current Input, Voltage Input and Thermocouple Input. Communicable over Modbus RTU and RS-485 with High Over Voltage Protection and cable. Supports operating temperatures between -25 to 75°C (-13F ~ 167F).  Includes DB-1820 Daughter Board.

M-7018Z - 10 Channel Voltage & Current Thermocouple Input Data Acquisition Module, High Over Voltage Protection & Cable

10 Channel Analog Input Data Acquisition Module, supports Current Input, Voltage Input and Thermocouple Input. Communicable over Modbus RTU and RS-485 with High Over Voltage Protection and cable. Supports operating temperatures between -25 to 75°C (-13F ~ 167F). Includes DB-1820 Daughter Board.

  Price:  $489.00  

Features

Application Image M-7018Z thermocouple input module The M-7018Z is a 10-channel voltage and current thermocouple input data acquisition module. It is communicable over Modbus RTU and RS-485 with High Over Voltage Protection. Supports operating temperatures between -25 to 75°C (-13F ~ 167F). M-7018Z comes with a DB-1820 Daugther Board that supports Modbus RTU. They can be remotely controlled using a set of commands called DCON protocol. With the Modbus RTU protocol, it can easily communicate with most popular SCADA software and PLCs.
  • Indication LED Light
    • For power and communication
  • Over voltage protection for M-7018R: 240Vrms
  • Supports Modbus RTU and DCON Protocol
  • 8 differential Analog Input Channels
  • Analog Input Types: mV, V , mA
  • Thermocouple: Type J, K, T, E, R, S, B, N, C
  • Din Rail Mount

Specifications

Analog Input
Input Channels 10 Differential
Input Type +/- 15mV, +/- 50mV, +/- 100mV, +/- 500mV, +/- 1V, +/- 2.5V
+/-20mA, 0~20mA, 4~20mA (Requires Optional External 125 Ohm Resistor)
Thermocouple (J, K, T, E, R, S, B, N, C, L, M, LDIN43710)
Resolution 16-bit
Sampling Rate 10 Samples/Sec (Total)
Accuracy +/- 0.1 %
-3dB BandWidth 15.7 Hz
Zero Drift +/- 0.5 μV/°C
Span Drift +/- 25 ppm/°C
Common Mode Rejection 150 dB
Normal Mode Rejection 100 dB
Input Impedance >500k Ohms
Over voltage Protection 240 Vrms
Open Thermocouple Detection Yes
Individual Channel Configuration Yes
Intra-module Isolation, Field to Logic 3000 VDC
Interface
Interface RS-485
Format N, 8, 1
Baud Rate 1200 ~ 115200 bps
DB-1820 (3.81mm pitch)
Wire Strip Length 4 ~ 5 mm
Wire Range 16 ~ 24 AWG
DN-1822 (5.08mm ptich)
Wire Strip Length 4 ~ 5 mm
Wire Range 14 ~ 24 AWG
LED Display
1 LED as Power/Communication Indicator
Power
Input +10 ~ +30 VDC
Power Consumption 1.0W
Protocol
Support Modbus and DCON Protocol Yes
Environment
Operating Temperature -25 ~ 75 °C
Storage Temperature -40 ~ 85 °C
Humidity 5 ~ 95% RH, Non-condensing

Thermocouple Type

Type Range°C
J -210 ~ +760
K -270 ~ +1372
T -270 ~ +400
E -270 ~ +1000
R 0 ~ +1768
S 0 ~ +1768
B 0 ~ +1820
N -270 ~ 1300
C 0 ~ 2320
L -200 ~ +800
M -200 ~ +100
L (DIN43710) -200 ~ +900

Related Products