8-Channel Analog Input Data Acquisition Module with High Over Voltage Protection, communicable over Modbus RTU, DCON and RS-485. Supports Current Input Types of +/-20mA, 0-20mA and 4-20mA. Supports operating temperatures between -25 to 75°C (-13F ~ 167F).

M-7017C - 8-channel Current Input Data Acquisition Module, Communicable over Modbus RTU and RS-485

8-Channel Analog Input Data Acquisition Module with High Over Voltage Protection, communicable over Modbus RTU, DCON and RS-485. Supports Current Input Types of +/-20mA, 0-20mA and 4-20mA. Supports operating temperatures between -25 to 75°C (-13F ~ 167F).

  Price:  $339.00  

Features

M-7017C is a 8-channel Analog Input data acquisition remote I/O module that supports Modbus RTU. It supports both current input types +/-20mA, 0-20mA and 4-20mA(requires optional external 125ohm resistor). With 240Vrms over-voltage protection and 4KV ESD Protection for each channel, it offers a safe and cost-effective solution for your data acquisition needs. It can be remotely controlled using a set of commands called DCON protocol. With the Modbus RTU protocol, it can easily communicate with most SCADA/ HMI software and PLCs.

  • LED Light Indicator
  • For power and communication
  • Over voltage protection: 240Vrms
  • Supports Modbus RTU and DCON Protocol
  • Din Rail Mountable
  • 8 differential Current Input Channels

M-7017 solarM-7017 I-7520

Specifications

Analog Input
Input Channels 8 differential
Input Type +/-20mA, 0-20mA and 4-20mA (requires optional external 125ohm resistor)
Resolution 16-bit (Normal Mode) / 12-bit (Fast Mode)
Sampling Rate 10 samples/ second (Normal Mode) / 60 samples/ second (Fast Mode) total
Accuracy +/-0.1% (Normal Mode) / +/-0.5% (Fast Mode) or better
Band Width 15.7Hz (Normal Mode) / 78.7Hz (Fast Mode)
Zero drift +/-20uV/°C
Span drift +/-25ppm/°C
Input Impedance 2M Ohms
Common Mode Rejection 86dB min.
Normal Mode Rejection 100dB
Over Voltage Protection 240 Vrms
4KV ESD Protection Yes, Contact for each terminal.
Intra-module Isolation, Field to Logic 3000 VDC
Interface
Interface RS-485
Format N, 8, 1
Baud Rate 1200 ~ 115200bps
LED Display
1 LED as Power/ Communication indicator
Power
Input +10 to +30 Vdc
Power Consumption 1.3W
Protocol
Support Modbus and DCON Protocol Yes
Watchdog Yes, Module, Communication (Programmable over DCON) firmware version B300 and later
Environment
Operating temperature -25 to 75°C
Storage temperature -40 to 85°C
Humidity 5 to 95% RH, non-condensing

Related Products


ICP DAS USA,Inc.