Digital Input (Counter)/Digital Output Data Acquisition Module (AC SSR type) with LED Display communicable over RS-485. Supports operating temperatures between -25°C ~ +75°C (-13°F ~ +167°F).

I-7063AD

Digital Input (Counter)/Digital Output Data Acquisition Module (AC SSR type) with LED Display communicable over RS-485. Supports operating temperatures between -25°C ~ +75°C (-13°F ~ +167°F).

  Price:  $289.00  

Fastest Delivery: (Details) X Delivery Details
We ship via UPS and fastest delivery is with Next Day Air. UPS Next Day Air Early typically gets their product to them as early as 8am, Next Day Air gets their product typically there by 10:30am and Next Day Air Saver typically by 3pm. We ship same day for in stock items and the lead time is up to one week for out of stock items. Delivery is dependent on UPS and your shipping method.
ADD TO CART
ADD TO CART
BUY BY 1-CLICK

Features

I-7063AD is intelligently designed to provide signal conditioning system monitoring and safe value settings. I-7063AD is a cost-effective solution for a wide range of valuable industrial control signals and systems. The DCON utility can help users to configure and test I-7063AD Isolated digital input & AC-SSR relay output module. Plenty of library functions and demo programs are provided to let users develop programs easily under Windows, Linux and DOS operating systems. The communication interface is modbus protocol via RS-485. Users may mount the modules on a DIN rail, panel or wall. Modules have a screw-terminal block to connect to the signals.

Specifications

Digital Input

  • Channels: 8
  • Digital Input level:
    Isolated with common power
    Logic level 0: +1V max.
    Logic level 1: +4V to+ 30V
    Isolation voltage: 3750Vrms
    Input impedance: 3KO , 0.5W
  • 8 Digital input channel with counter function
  • Input Frequency : 100Hz
  • 16-bit counter : 0-65,535
 
 
 
     
 

SSR AC output

  • Channels: 3
  • form "A” relay SPST (N.O.)
  • Dry contact
  • Characteristics
  • Contact rating:
    AC:24~ 265Vrms @1.0Arms
    Max. Load current 1.0Arms
    Min. Load current 10mArms
    Max. off-state leakage current
    0.75mA(at 100Vrms 60Hz)
    1.50mA(at 200Vrms 60Hz)
  • 1 Cycle surge current : 50A(60Hz)
  • Max. on-state voltage drop:1.2Vrms
  • Surge strength: 4,000Vac
  • Relay on time(Max.): 1ms
  • Relay off time(Min.): 1ms+1/2rms
  • Insulation resistance: 1,000MOhm min.at 500Vdc
  • Life time : long life, maintence free
 
 
 
     
 

Communication Interface

  • RS-485
 
 
 
     
 

Power Supply

  • Input Power: 10~30Vdc
  • Consumption :
    0.7W max. for I-7063A
    1.5W max. for I-7063AD