8-channel Isolated Thermocouple Input Redundant Module for DCS systems, 8 Samples/sec, supports operating temperatures from -25°C ~ +75°C

F-8019

8-channel Isolated Thermocouple Input Redundant Module for DCS systems, 8 Samples/sec, supports operating temperatures from -25°C ~ +75°C

  Price:  $1,899.00  

Fastest Delivery: (Details) X Delivery Details
We ship via UPS and fastest delivery is with Next Day Air. UPS Next Day Air Early typically gets their product to them as early as 8am, Next Day Air gets their product typically there by 10:30am and Next Day Air Saver typically by 3pm. We ship same day for in stock items and the lead time is up to one week for out of stock items. Delivery is dependent on UPS and your shipping method.
ADD TO CART
ADD TO CART
BUY BY 1-CLICK

Features

The F-8019 is a 16-bit, 8-channel thermocouple input module that features programmable input range on all channels. It measures millivolt input (±15mV, ±50mV, ±100mV, ±150mV, ±500mV), voltage input (±1V, ±2.5V, ±5V, ±10V) and thermocouple input (Type J, K, T, E, R, S, B, N, C). An external CJC is supported for accurate termperature measurement. Moreover, this module has ±0.05% accuracy for highly accurate application. Besides, the F-8019 provides 3000VDC optical isolation between channels and backplane bus. If any high voltage or current damages these channels, this module won’t affect other component in iDCS-8000 system.

  • 8 thermocouple input channels
  • User defined up/down scale
  • Open wire detection
  • RoHS compliance
  • 3000 VDC isolation from output to backplane
  • 3000 VDC isolation from output to frame ground
  • Redundancy
  • Fast redundant switching time (<100us)

Applications

  • Building Automation
  • Factory Automation
  • Machine Automation
  • Remote Maintenance
  • Remote Diagnosis
  • Testing Equipment

Specifications

Feature
Redundant Yes (Switching time < 100us)
Over Voltage Protection Yes
Resolution Yes
Sampling Rate Yes
Accuracy 1 RUN, 1 ACT, 1 DUX
Thermocouple Input
Number of channels 8
Type ±15mV, ±50mV, ±100mV, ±150mV, 
±500mV, ±1V, ±2.5V, ±5V, ±10V, 
Type J, K, T, E, R, S, B, N, C
Temperature Range J -210 ~ +1200 °C
K -270 ~ +1372 °C
T -270 ~ +400 °C
E -270 ~ +1000 °C
R -50 ~ +1765 °C
S -50 ~ +1765 °C
B 0 ~ +1820 °C
N -270 ~ +1300 °C
C 0 ~ +2320 °C
Maximum Allowable Input Voltage 120 VDC
Resolution 16 bit
Sampling Rate 8 Samples/sec (Total)
Accuracy ±0.05% FSR
Zero Drift ±0.5 μV/°C
Span Drift ±20 ppm/°C
Common Mode Rejection 106 dB
Normal Mode Rejection 90 dB
Input Impedance 10 MΩ
Data Range -2500 ~ 12500
Isolation 3000 VDC
Certification
EMC EN61000-6-2, EN61000-6-4, IEC/EN 61000-4-2, IEC/EN 61000-4-4
General
Termination board DN-TC-M
Maximum power consumption 1.3 W
Operating temperature -25°C ~ +75°C
Humidity 5 ~ 95 % RH, Non-condensing
Weight 300 g
Dimensions (W x L x H) 30 mm x 85 mm x 115 mm