Remote PM2.5/CO2/Temperature/Humidity/Dew Point Data Logger Module 

(RoHS)The CL-212 is a data logger module designed to accurately measure PM2.5, CO2, temperature and humidity. It contains RS-485 communication interface that can be used to measure a variety of PM2.5, CO2, temperature and humidity measurements. <br>

CL-212

Remote PM2.5/CO2/Temperature/Humidity/Dew Point Data Logger Module (RoHS)The CL-212 is a data logger module designed to accurately measure PM2.5, CO2, temperature and humidity. It contains RS-485 communication interface that can be used to measure a variety of PM2.5, CO2, temperature and humidity measurements.

  Price:  $739.00  

Features

Remote PM2.5/CO2/Temperature/Humidity/Dew Point Data Logger Module (RoHS)The CL-212 is a data logger module designed to accurately measure PM2.5, CO2, temperature and humidity. It contains RS-485 communication interface that can be used to measure a variety of PM2.5, CO2, temperature and humidity measurements. The data storage memory can store up to 450,000 PM2.5, CO2, temperature and humidity records. The Data Logger Utility is included to allow installation, configuration, retrieval and display of data in a powerful chart format that can be exported to Excel.

 

  • PM2.5, CO2, Temperature, Humidity and Dew Point Measurement
  • Non-dispersive Infrared (NDIR) CO2 Sensor
  • Up to 450,000 records with date and time stamps
  • Support DCON and Modbus RTU Protocols
  • Providing RS-485 Communication Interface
  • Relay Output for PM2.5/CO2/RH/T Alarm Output
  • Measurement Range
  • PM2.5: 0 ~ 400 μg/m3
  • CO2: 0 ~ 9999 ppms

Applications

  • Transportation of Food or Pharmaceuticals
  • Food and Beverage Industry (HACCP)
  • Blood Stations and Pharmacies
  • Building and Energy Management
  • Warehouse Management
  • Museums, Archives and Galleries

Reference & Support

Specifications

PM2.5 Measurement
Range 0 ~ 400 μg/m3
Resolution 1μg/m3
Response Time <= 1 min.
CO2 Measurement
Range
0 to 9999 ppm (NDIR)
Resolution
1 PPM
Accuracy
±30 ppm ±3% of measured value
Response Time
20 seconds
Warm Up Time
60 seconds
Temperature Measurement
Range
-10 to +50°C
Resolution
0.1°C
Accuracy
±0.6°C
Relative Humidity Measurement
Range
0 to 100% RH
Resolution
0.1% RH
Dew Point
Range
Calculated using temperature and relative humidity
Resolution
0.1°C
System
PM2.5/CO2/RH/T Alarm
Yes
Real Time Clock
Yes
Data Logger
Yes, up to 450,000 records
Relay Output
Form Ax1, SPST 30 VDC @ 16 A or 250 VAC @ 16 A
Interface/strong>
RS-485
Electrical
Powered from Terminal Block
+10 to +30 VDC
Power Consumption
1.2 W (Max.)
Mechanical
Installation
Ceiling Mounting
Protection Class
IP20
Dimensions (D x H)
Ø 150 mm x 53 mm
Environment
Operating Temperature
0 to +50°C
Storage Temperature
-30 to +75°C
Humidity
10 to 90% RH, Non-condensing

Related Products


ICP DAS USA,Inc.